Copper tube: two systems, one millimetre apart

US copper (ASTM B88) is named by nominal size but measures nominal + 1/8″ outside; wall thickness picks the type — K (thick), L (medium), M (thin) — while OD stays constant. European copper (EN 1057) is named by its actual OD in mm. The trap: a measured 15.0 mm tube is European; 15.88 mm is US ½″. One millimetre decides which fittings fit.

US — ASTM B88 (Type K / L / M)

NominalOD (in)OD (mm)K wallL wallM wall
1/4″0.375″9.520.035″0.030″
3/8″0.500″12.700.049″0.035″0.025″
1/2″0.625″15.880.049″0.040″0.028″
5/8″0.750″19.050.049″0.042″
3/4″0.875″22.220.065″0.045″0.032″
1″1.125″28.570.065″0.050″0.035″
1-1/4″1.375″34.920.065″0.055″0.042″
1-1/2″1.625″41.270.072″0.060″0.049″
2″2.125″53.970.083″0.070″0.058″

Europe — EN 1057

OD (mm)Common wall (mm)Replaces old imperial
60.5–1.0
80.5–1.0
100.5–1.03/8″
120.5–1.0
140.7–1.0
150.7–1.01/2″
160.8–1.0
180.8–1.0
220.9–1.23/4″
280.9–1.51″
351.0–1.51-1/4″
421.0–1.51-1/2″
541.2–2.02″
66.71.2
76.11.5–2.0
1081.5–2.5

EN 1057 walls vary with tube type (X/Y/Z) and national practice — the OD is the constant to identify by. Full EN diameter family runs 6–267 mm; the table shows plumbing-common sizes.